Handbook Ucontrol type-lines PXDM Date 06/04
TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 30 / 105
1.01
Speed controller
IO Setup
F
¨
A Function (output 0-10 V)
1 A: Constant voltage 10 V
2 A: proportional modulation
3 A: proportional signal E1
4 A: proportional signal E2
5 A: Group control
¨
D1 / D2 Function (Digital Inputs)
1 D: Enable ON/OFF
2 D: External fault
3 D: Limit ON/OFF
4 D: Switch over: Signal E1 / E2
5 D: Switch over Set Intern 1 / 2
6 D: Switch over: Set intern / Set extern
¨
K1 / K2 Function (Relay out)
1 K: Operating indication
2 K: Fault indication
3 K: external fault
4 K: Limit modulation
5 K: Limit E1
6 K: Limit E2
8 K: Group control
Limits
¨
L Function (Limits)
1 L: Indication with centralized fault
2 L: Indication as Message
¨
E2 Function (Analog IN 2)
1E: switch over E1 / E2 by digital contact
4E: automatic control to higher value E1 or E2
(special functions with second signal)
8.2.5 Factory setting for mode 1.01 (preprogrammed) and user setting
Parameter Factory
setting
User
Setting
Set Intern 1 80 %
Set Intern 2 --
Min. Speed 0 %
Max. Speed 100 %
Set external 1 ON
Setting
Mode 1.01
E1 Analog IN 0-10 V
E2 Function OFF
E2 Analog IN -----
Base setup
PIN-Protection OFF
Set protection OFF
Save user Setup OFF
Limit -----
On Value Group2 -----
N min at Group2 -----
ControllerSetup
A Function 1 A
A min 0.0V
A max 10.0 V
A Inverting OFF
D1 Function OFF
D1 Inverting --
D2 Function OFF
D2 Inverting --
E1 Inverting OFF
E2 Inverting -----
K1 Funktion 1 K
K1 Inverting OFF
K2 Function 2 K
K2 Inverting OFF
IO Setup
BUS Address 247
Level Function OFF
Level min. -----
Level max. -----
Level Delay -----
Lmt E1Function OFF
Lmt E1 min. -----
Lmt E1 max. -----
Lmt E1 Hyst. -----
Lmt E1 Delay -----
Lmt E2 Function -----
Lmt E2 min. -----
Lmt E2 max -----
Lmt E2 Hyst. -----
Limits
Lmt E2 Delay -----
Cos Phi 0.80
Rampup time 20 sec.
Rampdown time 20 sec.
Suppression 1 OFF
Range 1 Min. -----
Ragne 1 Max. -----
Suppression 2 OFF
Range 2 Min -----
Range 2 Max. -----
Suppression 3 OFF
Range 3 Min -----
Range 3 Max. -----
Motor Setup