8.3 Temperature control mode 2.01 .. 2.05
8.3.1 Basic setting 2.01 .. 2.05
Basic device settings are carried out in two steps:
1 Place the internal plug (jumper) for the external default signal in the correct position. Caution – not under voltage!
Observe the safety notices!
2 Switch the voltage on and select mode of operation (general controller function) factory setting 1.01 = speed controller.
If necessary configuration of sensors.
1
Type of signal Input Analog IN 1 INFO
0-10 V No PINs
with Jumper
bridged
Temperature sensor with aktiv signal
Factory setting!
0-20 mA / 4-20 mA Lower PINs
with Jumper
bridged
Temperature sensor with aktiv signal
TF.. (KTY10-6) Upper PINs
With Jumper
bridged
Passive Temperature sensor type KTY10-6
For Ziehl-Abegg Sensors TF.. put in up
position
Connection of a temperature sensor type TF..to „Analog IN 1“
(passive temperature sensor whose resistance changes with the temperature)
Input 2 is automatically activated upon selection of operating modes with 2-sensors
2.04 and 2.05. The jumpers E 2.1 (J2)
and E 2.2 (J3) must be inserted in accordance with the sensor signal.
For sensors type TF.. at Analog IN 2
J4
J5
E1.1 E1.2
J4
J5
E1.1 E1.2
J4
J5
E1.1 E1.2
Sensor TF.. KTY10-6
(KTY11-2a)
GND
E1
Sensor TF.. KTY10-6
(KTY11-2a)
GND
E2
J2
J3
E2.1 E2.2