EasyManua.ls Logo

ZIEHL-ABEGG Ucontrol PXDM35A - Pressure Control for Ventilation Systems 4.01, Setpoint Depending on Outdoor Temperature 4.02

ZIEHL-ABEGG Ucontrol PXDM35A
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Handbook Ucontrol type-lines PXDM Date 06/04
TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 51 / 105
8.5 Pressure control for ventilation systems 4.01, setpoint depending on outdoor temperature 4.02
8.5.1 Basic setting 4.01 and 4.02
1 Place the internal plug (jumper) for the external default signal in the correct position. Caution – not under voltage!
Observe the safety notices!
2 Switch the voltage on and select mode of operation (general controller function) factory setting 1.01 = speed controller.
If necessary configuration of sensors.
1
Type of signal Input Analog IN 1 INFO
0-10 V
No PINs with
jumper bridged
Factory setting for pressure sensors with 0-10 V
signal proportional to measuring range
e. g. Ziehl-Abegg sensors DSG..
0-20 mA /
4-20 mA Lower PINs with
jumper bridged
Pressure sensors 0-20 mA or 4-20 mA proportional to
measuring range
Connection for pressure sensor type DSG..at „Analog IN 1“
Input 2 is automatically activated upon selection of operating mode with 2-sensors
4.02. The jumpers E 2.1 (J2) and E 2.2
(J3) must be inserted in accordance with the sensor signal.
Passive Temperature sensor type KTY10-6
For Ziehl-Abegg Sensors TF.. put in up position
TF..
(KTY10-6)
Upper PINs
with Jumper
bridged
Passive Temperature sensor type KTY10-6
For Ziehl-Abegg Sensors TF.. put in up position
for active sensors as for sensor at E1
for sensors type TF.. at „Analog IN 2“
J4
J5
E1.1 E1.2
J4
J5
E1.1 E1.2
Sensor DSG..
(0-10 V)
E1
24V
GND
br ge ws
BN YE WH
DSG..
Sensor TF.. KTY10-6
(KTY11-2a)
GND
E2
υ
J2
J3
E2.1 E2.2

Table of Contents

Related product manuals