Handbook Ucontrol type-lines PXDM Date 06/04
TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 57 / 105
4.01
Pressure control
- Setpoint in Pa (mbar)
4.02
Pressure control for ventilation systems
setpoint depending on outdoor
temperature
- Setpoint in Pa (mbar)
and temperature adjustment in °C
IO Setup
F
¨
A Function (output 0-10 V)
1 A: constant voltage 10 V
2 A: proportional modulation
3 A: proportional signal E1
4 A: proportional signal E2
5 A: Group control
¨
D1 / D2 Function (digitale inputs)
1 D: Enable ON/OFF
2 D: External fault
3 D: Limit ON/OFF
4 D: Switch over: Signal E1 / E2
5 D: Switch ofer Setpoint 1 / 2
6 D: Switchover: Internal / External
7 D: Controlling /Manual internal
8 D: Switch over: actualValue>Set=n+/n-
¨
K1 /K2 Function (Relay out)
1 K: Operaiting indication
2 K: Fault indication
3 K: external fault
4 K: Limit modulation
5 K: Limit E1
6 K: Limit E2
7 K: Setpoint Offset
8 K: Group control
8.5.7 Factory setting and user setting for modes 4.01 - 4.02
Parameter Factory setting User
Setting
Setpoint 1 100 Pa 100 Pa
Setpoint 2 ----- -----
Pband 100 Pa 100 Pa
Min. Speed 0 % 0 %
Max. Speed 100 % 100 %
Manual mode OFF OFF
Speed manual 100 % 100 %
T-Band SD 30 K
T- Start SD 15 °C
P-min SD 70 Pa
Setting
Mode 4.01 4.02
E1 Analog IN
200 DSG 200 DSG
E1 Min. ----- -----
E1 Max. ----- ------
E1 Decimal ----- ------
E1 Unit ----- -----
E1 Offset 0.0 Pa 0.0 Pa
E2 Function
OFF 6 E
E2 Analog IN ------ TF
E2 Min. ----- -----
E2 Max. ----- -----
E2 Unit ------ -----
E2 Unit ----- -----
Base setup
E2 Offset ----- 0.0 K
PIN-Protection OFF OFF
Set Protection OFF OFF
Save user Setup OFF OFF
Alarm Sensors OFF OFF
Limit ----- -----
Msco OFF OFF
ON value Group2 ----- -----
n-min atGroup2 ----- -----
actVal > Set = n+ OFF OFF
Type of control PID PID
KP 50 % 50 %
KI 50 % 50 %
KD 50 % 50 %
TI 0 % 0 %
Controller Setup
A Function 1 A 1 A
A min 0.0V 0.0V
A max 10.0 V 10.0 V
A Inverting OFF OFF
D1 Function OFF OFF
D1 Inverting -- --
D2 Function OFF OFF
D2 Inverting -- --
E1 Inverting OFF OFF
E2 Inverting -- OFF
K1 Function 1 K 1 K
K1 Inverting OFF OFF
K2 Function 2 K 2 K
K2 Inverting OFF OFF
IO Setup
BUS Address 247 247
¨
E2 Function (Analog IN 2)
F
1 E: 0-10 V external Setpoint
2 E: external manual mode
3 E: Sensor average to E1
(only for mode 2.04 alternative)
4 E: Sensor comparison to E1
5 E: Sensor difference to E1
6 E: Sensor for Setpoint lowering
(only for Mode 4.02 and 5.02)