8.6.2 Function analog Input 2 (Analog IN 2 ) second Sensor, external Setpoint, extern manual operation
The function is automatically jointly programmed in operating modes using 2 sensors. The second analog input is thus
allocated and additional function allocations are not possible
Modes with two sensors
5.02
E2 Funktion to 6E
preprogrammed = sensor for setpoint lowering.
preprogrammed sensor type TF..
Possible functions with a free analog input 2 (Analog In 2)
External Setpoint or external speed setting in manual operation with a 0-10 V (0-20 mA, 4-20 mA) signal is possible on
the „E2" and „GND" terminals. Correspondingly insert jumpers E2.1 and E2.2 for analog IN 2 and configure E2 in base
setup.
For potentiometer analog OUT 1 (terminal „A“), program to function 1A (factory setting) = +10 V F IO Setup: Analog
output function.
External Setpoint via external signal (0-10 V, 0-20 mA, 4-20 mA) instead of „Setpoint 1“
The „External Setpoint“ function must be activated in base setup 1E
for E2 function; Set Intern 1 then has no function. A
switchover „Ext. Setpoint“ / „Set Intern 2“ is still possible.
0-10 V (4-20 mA, 0-20 mA) Setting value = 0-100 % sensor measurement range
The active external Setpoint value is displayed in the info menu group
External speed setting in manual operation (F IO Setup Internal / External).
The „External manual operation“ function must be activated in the basic settings 2E
for E2 function. Switchover between
settings on the device and external manual operation via the digital input (F IO Setup: Internal / External).
Jumper position for:
0-20 mA bzw. 4-20 mA Signal
Jumper position factory setting
for 0-10 V signal
Analog IN 2
J2
J3
E2.1 E2.2
Analog IN 2
J2
J3
E2.1 E2.2
Signal 0-10 V
GND
A
1k
E2