3. General description
3.1 Scope of applications
The controlling device as described is intended for infinitely variable speed settings in voltage-regulated 3-phase motors
for driving fans and pumps.
3.2 Technical data
Type Part-No. Rated
current *
[A]
Max. line
fuse
{1}
[A]
Semi-
conductor
fuse {2}
(Part-No.)
Heat
dissipation
[W]
Weight
[kg]
Housing
protection
PXDM5 304561 2.3
PXDM5A 304564
510
Internal
FF20 A 6x32mm (00089798)
approx. 40
2.4
IP54
PXDM10 304562 2.7
PXDM10A 304565
10 16
Internal
FF20 A 6x32mm (00089798)
approx. 50
2.8
IP54
PXDM12 304571 3.4
PXDM12A 304572
12 16
Internal
FF30 A 10x38mm (00155987)
approx.. 60
3.5
IP54
PXDM15 304563 4.75
PXDM15A 304566
15 20
Internal
FF30 A 10x38mm (00155987)
approx. 85
4.8
IP54
PXDM25 305534 12.7
PXDM25A 305536
Integriert
FF50 A D02 (00091006)
12.8
IP54
PXDM25E 305549 7.2
PXDM25AE 305553
25 35
construction site
FF50 A D02 (00091006)
approx. 130
7.3
IP20
PXDM35 305535 12.9
PXDM35A 305537
Internal
FF63 A D02 (00089795)
13
IP54
PXDM35E 305550 7.4
PXDM35AE 305554
35 50
construction site
FF63 A D02 (00089795)
approx. 210
7.5
IP20
PXDM50 305565 20
PXDM50A 305567
Internal
FF100 A NH00 (00150320)
20
IP54
PXDM50E 305590 13,8
PXDM50AE 305592
50 63
construction site
FF100 A NH00 (00150320)
approx. 230
13,8
IP20
PXDM80 305566 21
PXDM80A 305568
Internal
FF160 A NH00 (00089793)
21
IP54
PXDM80E 305591 15,4
PXDM80AE 305593
80 100
construction site
FF160 A NH00 (00089793)
approx. 350
15,4
IP20
* at line voltage 400 V / 50 Hz
{1}
Max. supply side line fuse according to DIN EN 60204-1 classification VDE0113 chapter 1
{2}
Enclosed version IP54 with internal semiconductor fuse (no line protection)
Built in version for switch cabinets (IP20) semiconductor fuse installation on site recommended. Protection for damages
in the case
of short-circuits. Not in the scope of supply!