EasyManua.ls Logo

ZIEHL-ABEGG Ucontrol PXDM35A - Set Intern 1; Set Intern 2 Or. Setpoint 1;2 Function 5 D

ZIEHL-ABEGG Ucontrol PXDM35A
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Handbook Ucontrol type-lines PXDM Date 06/04
TBL02_55-GB06/04 Part.-No. 00153239-GB
Page 86 / 105
10.2.5 Set Intern 1 / Set Intern 2 or. Setpoint 1/2 Function 5D
¨ Switch over between Set Intern 1 and Set Intern 2 (for speed controller 1.01)
Operation with “Internal default 2“ is signalized by the moon symbol for reduced operation.
“Set external 1“ under settings must be programmed to OFF
contact at digital input e. g. Digital IN 1 = D1-D1
Set Intern 1 at opened contact Set Intern 2 at closed
contact D1 Inverting OFF
Set Intern 1 at closed contact Set Intern 2 at closed contact D1 Inverting ON
¨ Switch over between Setpoint 1 and Setpoint 2 (for modes as controller higher 2.01)
operation with „Setpoint 2“ is signalized by the moon symbol for reduced operation.
contact at digital input e. g. Digital IN 1 = D1-D1
Setpoint 1 = 18° C at opened contact Setpoint 2 = 25° C at closed
contact D1 Inverting OFF
Setpoint 1 = 18° C at closed contact Setpoint 2 = 25° C at opened contact D1 Inverting ON
Controller
3~ 400 V
D1 D1
0
1
3~ 0-100 %
Sensor
Controller
3~ 400 V
3~ 78 % = Intern 1
D1 D1
0
1
0
1
3~ 40 % = Intern 2

Table of Contents

Related product manuals