10.2.7 Automatic control / speed manual internal (Menu Speed maunal) Function 7D
Switch over between automatic control to set target value (depending on the activation: Setpoint 1, Setpoint 2, Setpoint
external) and the default for manual operation set at the device.
Contact at digital input e. g. Digital IN 1 = D1-D1
Automatic control at opened contact manual operation at closed
contact D1 Inverting OFF
Automatic control at closed contact manual operation at opened contact D1 Invertierung ON
10.2.8 Reverse action of control function actual value>Set = n+ or actual value>Set = n- Function 8D
Switchover between: Increasing modulation during increasing actual-value and increasing modulation during sinking
actual-value.
The factory presets for the “Control function“ are dependent on the selected mode of operation (
F Controller Setup
reverse operation of the control function.)
When switching over via a digital input, the device works with the opposite function than the one set there!
Example: Actual value>Set = n+ (increasing modulation during increasingg actual value)
contakt at digital input e. g. Digital IN 1 = D1-D1
Setting in Controller Setup
contakt at digital input e. g. Digital IN 1 = D1-D1
actual Value>Set = n+ at opened contact actual > Set = n- at closed
contakt D1 Inverting OFF
actual Value>Set = n+ at closed contact actual > Setl = n- at opened contact D1 Inverting ON
Controller
3~ 400 V
D1 D1
0
1
3~ 0-100 %
Sensor
external Setpoint or
external manual mode
Signal 40 %
Controller
3~ 400 V
3~ 100 %
D1 D1
E2
0
1
Intern
Extern
INTERN = 0
EXTERN = 1
Sensor
0
1
E1