Loading...
Step
1/2" (13 mm)
Mastic Strip
Clean and Lubricate
Attach Ground
Lead to Elbow
Grounding Tab
Step
Cold Shrink Tubing
Counter-Clockwise
7.5 7.6
7.5 Remove white liners from remaining mastic strip and
apply around base of elbow,
1
2
" (13 mm) from step as
shown. Apply 1 layer of vinyl tape over mastic.
7.6 Align Cold Shrink rubber tube (not core) with step of
elbow. Remove core by pulling and unwinding the
core counter-clockwise.
Attach 14 AWG ground lead (from ground braid
assembly) to the elbow grounding eye. Connect
ground braid to system ground. (For jacketed
concentric neutral cable, attach a neutral strand to
grounding eye, and connect remaining neutral bundle to
system ground.)
9
78-8124-4544-9-B
Connector
5
/
8
" Diameter
3
/
4
" Diameter
Conductor Size 4 AWG through 2/0 Stranded 3/0 AWG through 250 kcmil Stranded
Tool Y34 Y35 OR Y39 MD6 Y34 Y35 OR Y39 MD6
A243 U243 UBG W243 WBG U247 U247 U467 W247
Burndy Die
A25AR U25ART U687 BG W687 A27AR
U27ART
Nose
Thomas Tool
UT-3 UT-5 UT-15 UT-5 UT-15
& Betts Die
5
/
8
" TV 54 H TV 66
Kearney Tool
0 H-1, H-2 0 H-1, H-2
Die
5
/
8
"
Nose
9
/
16
"
9
/
16
" 572 737 747 737 747
Alcoa Tool 12A 12A
Die B24 EA B39 EA
Anderson Tool VC-5, VC-6 VC-5, VC-6
EEI—Reference 8A 10A
Table 2.
Crimp Chart.