ABB Power Capacitors | Portable Capacitance Meter CB-2000 — User´s Guide 45
9. Trouble shooting
Program
Problem Cause Remedy Section
The CB-2000 not detected by computer
Message “No CB-2000 present”
is displayed.
Drivers for CB-2000 are not
installed.
Install drivers. 2.1
USB cable is not
connected.
Connect USB cable and
switch on CB-2000.
5
CB-2000 is not
switched on.
Switch on CB-2000. 5
Error messages appear while trying to upload data to the CB-2000.
“Illegal date and time stamp detected”
Date and time format should
be:
YYYY-MM-DD hh:mm:ss
Correct date and time
stamp to the required for-
mat or leave input blank.
5.3
“Illegal capacitance value detected”
Only digits and a decimal
separator are accepted.
Correct the capacitance
values to the required for-
mat or leave input blank.
5.3
“Illegal temperature value detected”
Only digits are accepted. Correct temperature value
to the required format or
leave input blank.
5.3
The first capacitor is missing in the
CB-2000 program.
The first line is expected to be
a header line and is ignored
while opening a data file.
Add an extra line at the
beginning of the data file.
5.3
Warning message appears while trying to upload data to the CB-2000.
“Upload is limited to 1000 rows,
upload is cancelled”
A maximum of 1000 capacitor
units can be stored in the
CB-2000.
Reduce the number of
rows to 1000 or less.
4.3