EasyManua.ls Logo

ABB CT-AHS - Operating Controls and Electrical Connections; CT-MXS Function Selection; Terminal Function Descriptions; CT-ARS Specific Notes

ABB CT-AHS
25 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I Front view with operating controls
a
Adjustment of the time range (depending on the device)
by selecting the max. value of the desired time range:
Time range: Yellow scale:
0.15 - 3 s = 3 s
1.5 - 30 s = 30 s
15 - 300 s = 300 s
1.5 - 30 min = 30 m
15 - 300 min = 300 m
1.5 - 30 h = 30 h
15 - 300 h = 300 h
Time range: White scale:
0.05 - 1 s = 1 s
0.5 - 10 s = 10 s
5 - 100 s = 100 s
0.5 - 10 min = 10 m
b
Direct reading scale to set the time value within the
chosen range
- Yellow scale: 1.5 - 30
- White scale: 0.5 - 10
If the value on the scale “T Range” is yellow
use yellow time values on the scale “Time”
If the value on the scale “T Range” is white
use white time values on the scale “Time”
Calculation of the time value:
“T Range” Value on scale “Time”
1 s, 3 s x 0.1 = Time value
10 s, 30 s, 10 m, 30 m, 30 h x 1 = Time value
100 s, 300 s, 300 m, 300 h x 10 = Time value
Example 1:
Time value to set: 0.2 s
Select 3 s on yellow scale “T Range”
Select 2 on yellow scale “Time”
2 x 0.1 = 0.2 s
Example 2:
Time value to set: 80 s
Select 100 s on white scale “T Range”
Select 8 on white scale “Time”
8 x 10 = 80 s
c
Function on CT-AHS, CT-ARS, CT-APS, CT-ERS /
Selection of the function on CT-MBS, CT-MFS, CT-MVS,
CT-WBS
Functions: see III
d
Setting of the 2nd c/o contact as an instantaneous
contact
Position Inst. “I”: Instantaneous contact
e
Indication of operational states with LEDs
U/T: green
LED
- Status indication of control supply
voltage and timing
V
Control supply voltage
applied
W
Time delay is running
(not on CT-ARS)
R: yellow LED - Status indication of output relay
V
energized
R1/R2: yellow LED
- Status indication of output relays
1 and 2
V
energized
f
Selection of the function on CT-MXS
1 ON = Single pulse generator, starting with OFF
2 ON = ON-delay and OFF-delay, asymmetrical
3 ON = Impulse-ON and impulse-OFF
4 ON = No function
All ON = ON/OFF-function
All OFF = Pulse generator, starting with ON or OFF
Default setting:
All DIP switches in position OFF
II Electrical connection
For the rated control supply voltage and the
circuit diagram, see label at the side of the unit.
A1-A2 Control supply voltage Us
A1-Y1/B1 Control input to start timing
(voltage-related triggering)
Y1-Z2 Control input to start timing
(voltage-free triggering)
X1-Z2 Control input to pause timing / accumulative
function (see function diagram 19)
Z1-Z2 Remote potentiometer connection for the fine
adjustment of the time delay. When an external
potentiometer is connected, the internal, front-
face potentiometer is disabled.
Z2-Z3/Z1 1st/2nd remote potentiometer connection for
the fine adjustment of the time delay.
When an external potentiometer is connected, the
corresponding internal, front-face potentiometer
is disabled.
15-16/18 1st c/o contact
25-26/28 2nd c/o contact
21-22/24 2nd c/o contact, set as instantaneous contact
17-18 1st n/o contact
17-28 2nd n/o contact
CT-ARS:
Prior to first commissioning and after a storage time of more
than 6 months without any voltage, a formatting time of about
5 minutes is necessary!
Only after applying control supply voltage for the first time, the
output contacts will take their correct switching position.
English
Page 13/25

Related product manuals