Either
an
OR
or
an
AND
interlocking
logic
can
be
used
(see
parts
of
the
ordering
code
headed
EKl
or
EK2
in
the
tables
of
features
Table
9
.17,
Table
9.18
and
also
Fig.
9.25).
The
LED
signal
labelled
"E"
will
only
light
up
when
both
the
earth
fault
detector
and
at
least
one
underimpedance
phase
element
have
picked
up.
3.2.2.2
Reach
of
the
underimpedance
elements
8
standard
characteristic
The
standard
under
impedance
starting
characteristic
is
a
circle
with
its
centre
at
the
origin
of
the
impedance
plane.
The
relationships
for
an
earth
fault
R-0
are:
-
ULiR
-
Ul:R
-
·goo
--
UR
-
2
X
eJ
IR
A
-
j90
-
u +
2
XBe
IR
R
XA
=
XB
replica
reactance
in
forward
direction
replica
reactance
in
backward
direction
Criterion
for
pick-up:
u:R
j_
The
reach
for
radial
lines
and
the
different
kinds
of
faults
is:
-
phase-to-phase
fault:
same
as
setting
-
three-phase
fault
-
earth
fault
2
: x
setting
13
2
1 + k
oL
x
setting
(k = K
of
the
line)
oL o
ABB
has
a
computer
programme
for
checking
the
relay
settings
for
all
kinds
of
faults
and
fault
locations
where
complex
system
conditions
prevail.
The
starters
must
reliably
pick
up
for
a
fault
at
the
end
of
the
next
section
of
line
(back-up
zone).
Where
the
back-up
zone
is
not
being
taken
specifically
into
account,
the
setting
must
be
at
least
1.
3
times
the
impedance
of
the
protected
line.
The
influence
of
arc
resistance
must
also
be
considered
in
the
case
of
short
lines.