ABB Modures LZ92-1 - OPERATION AND MAINTENANCE GUIDE

ABB Modures LZ92-1
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
As
soon
as
one
or
more
of
the
test
buttons
(R,
s
or
T)
are
pressed,
the
corres-
ponding
starting
unit
or
units
pick
up
and
the
auxiliary
tripping
relay
is
interlocked
to
prevent
operating
the
circuit-breaker
inadvertently.
The
starting
units
apply
phase
quantities
to
the
measuring
unit
according
to
the
kind
of
fault
being
simulated.
The
relay
will
pick
up
in
some
stage
or
other
depending
on
the
load
current
at
the
time
and
the
relay
settings.
(If
the
values
and
phase-angle
of
the
load
quantities
is
known,
it
is
even
possible
to
test
the
various
zones
by
suitably
changing
the
settings.)
Providing
the
fourth
zone
is
non-directional,
the
relay
must
at
very
least
pick-up
in
the
fourth
zone
(red
LED
lights
up)
The
fourth
zone
must
be
made
directional
and
all
the
zones
be
measuring
in
the
forwards
direction
in
order
to
check
the
relay's
ability
to
determine
direc-
tion.
The
corresponding
switch
positions
are:
switch
Ba
in
position
1,
switch
Sb
in
position
1
or
2
depending
on
input
transformer
connection
and
switch
7
in
position
1.
Caution!
Units
may
only
be
withdrawn
from
the
rack
when
the
auxiliary
supply
is
switched
off.
Under
the
above
conditions
the
relay
must
pick
up
when
the
load
energy
is
flowing
in
the
forwards
direction
and
block
when
the
energy
direction
is
reversed
by
operating
switch
Sb
(part
number
HESG
439
686)
or
the
frontplate
switch
I~
(part
number
HESG
440
718),
or
vice
versa.
The
ability
of
the
relay
to
pick
up
and
block
must
be
tested
in
this
way
for
all
kinds
of
faults.
Withdrawing
a
relay
with
non-directional
fourth
zone
can
be
avoided
by
setting
the
thumbwheel
switch
N
of
the
corresponding
zone
to
0%
(infinite
reach).
Should
the
direction
be
incorrect
for
a
particular
kind
of
fault,
the
polarity
of
al
1
c.
t'
s,
p.
t
's,
leads
and
connections
must
be
checked
(see
Sections
5.
3
and
5.4).
If
the
direction
is
incorrect
for
all
kinds
of
faults,
all
the
current
connections
must
be
reversed.
In
the
case
of
relays
LZ92
and
LZ92-1
with
off-set
starting
characteristics
care
must
be
taken
that
the
longest
reach
of
the
starters
is
in
the
desired
direction
(see
Section
3.6).
Provision
is
made
on
the
input
transformer
unit
EW91
from
part
number
HESG
440
754
to
apply
a
signal
manually
to
the
auxiliary
tripping
relay
and
thus
trip
the
circuit-breaker.
This
operation,
however,
is
interlocked
for
safety
rea-
sons.
Firstly
terminal
Ell
of
the
input
transformer
unit
must
be
connected
to
terminal
E63
of
the
main
processing
unit.
Then
the
sockets
&
and->\'-
must
be
connected.
Finally
a
starting
button
must
be
pressed.
It
is
not
possible
to
test
the
tripping
circuit,
if
the
connection
Ell-E63
is
not
made.
(