7.
OPERATION
AND
MAINTENANCE
38
Where
no
remote
reset
is
fitted,
the
LED
signals
must
be
reset
each
time
the
relay
picks
up
(providing
the
signals
are
in
operation,
i.e.
main
processing
unit
code
FAl).
Please
refer
to
Section
3.11
for
main
processing
units
with
PCB
8
ace.
to
HESG
440
718
The
relay
continues
to
operate
correctly
whether
the
signals
are
reset
or
not,
but
the
signals
may
no
longer
be
related
to
the
fault
concerned.
The
relay
requires
no
special
maintenance.
However,
as
is
usual
with
all
safety
systems,
it
should
be
tested
at
regular
intervals.
This
can
be
carried
out
as
described
in
Section
6.5.
The
test
buttons
on
the
frontplat.e
permit
a
simple
functional
test
to
be
carried
out
with
the
relay
connected
to
load
quantities.
The
latter
can
also
be
measured
at
the
test
sockets
on
the
front.plate.
Furthermore
the
tripping
circuit
inclu-
ding
the
circuit-breaker
can
be
tested
with
input
transformer
units
with
oart
number
HESG
440 754
resp.
441
721
and
main
processing
unit
with
PCB
8
ace.
to
HESG
440
718.
Since
the
simple
tests
above
can
be
carried
out
at
relatively
short
intervals,
comprehensive
testing
with
a
test
set
is
only
necessary
at
two-yearly
intervals.
But
quantitive
testing
is
essential
after
this
period
regardless
of
whether
the
relay
is
equipped
with
a
test
socket
XX91
or
not.
Where
it
is
not,
either
signals
must
be
injected
at
the
terminals
after
appropriately
isolating
the
main
c.
t
's
and
p.
t'
s,
or
the
plug-in
uni
ts
can
be
withdrawn
and
inserted
into
a
separate
equipment
rack
wired
to
the
test
set.
7.1
Ancillaries
and
spares
When
ordering
ancillaries
and
spares,
it
is
essential
that
the
type
and
serial
number
of
the
unit
for
which
they
are
intended
be
stated.
If
a
number
of
identical
relays
are
installed
in
a
plant,
we
recommend
stocking
spare
units.
Spares
must
be
stored
in
a
clean
dry
room
at
moderate
temperatures.
It
is
further
recommended
that
spares
also
be
tested
at
the
same
time
as
the
periodic
testing
of
the
protective
equipment
in
operation,
i.e.
every
one
or
two
years.

Related product manuals