The
operating
mode
is
set
on
the
main
processing
unit
KZ91-1
with
the
aid
of
switch
1
(Fig.
9.23).
This
switch
has
four
sections
which
have
to
be
set
in
accordance
with
Table
3
.1.
'l'he same
information
is
printed
on
the
frontplate
behind
the
withdrawing
handle
(Fig.
9.8).
switch
section
*
Mode
-
No.
1
No. 2 No.
3 No.
4
Phase
preference
Setting
OFF
ON
ON
OFF
grounded
systems
±
OFF
OFF
ON
OFF
R'rS
acyclically
RTS
acyc.
ON
ON
OFF OFF
RTSR
cyclically
R'l'SR
eye.
OFF
ON
OFF OFF
TRS
acyclically
TRS
acyc.
ON
OFF
OFF OFF
TRS'l'
cyclically
TRST
eye.
ON
OFF
ON
OFF
TSR
acyclically
TSR
acyc.
ON ON
ON
ON
RST
acyclically
RST
acyc.
OFF
OFF OFF
OFF
STR
acyc
lie
ally
**
STR
acyc.
OFF
OFF OFF
ON
SRT
a<:Y_<:l_i_~~l
_
_1-y
**
SRT
acyc.
*
In
position
"ON"
the
white
lever
is
toward
the
PCB.
**
Only
for
units
with
the
designation
"AEND.
:B"
on
PCB
1.
Table
3.1
-
Positions
of
the
switch
sections
of
switch
1
on
PCB
1
of
unit
KZ91-1
in
relation
to
operating
mode
3.2
Setting
the
starting
units
3.2.1
Overcurrent
starting
6
The
pick-up
setting
of
the
overcurrent
uni
ts
must
be
at
the
very
least
so
high
that
it
cannot
be
reached
by
the
maximum
current
in
healthy
phases.
The
following
must
be
taken
into
account
when
calculating
this
current:
-
In
the
case
of
double-circuit
lines
the
load
current
can
briefly
double
when
one
line
is
tripped.
-
An
additional
balancing
current
IA
can
flow
in
the
healthy
phases
during
earth
faults.
A
relay
which
has
picked
up
must
also
be
able
to
reset
at
the
level
of
the
maximum
load
current
I
after
a
fault
has
been
tripped
in
the
first
zone
Bmax
.
of
another
relay.
Taking
the
reset
ratio
and
accuracy
of
the
relay
into
account,
the
lowest
permissible
setting
is
given
by:
lr;max
+~I
~~~~~~~-
+
0.06
The
maximum
pe.rmissible
setting
(I/I
)
is
calculated
from
the
minimum
fault
current
IK
for
a
fault
at
the
rerWo.r~xend
of
the
next
section
of
line.
(