Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
42
Table 19: General
Toolboxes CAP 501
CAP 505
LNT 505
Event recording all events are recorded in higher level syntax:
reason, time, date
the last 100 events are recorded
Data recording records operate values
Protection functions
Control functions
Condition monitoring functions
Measurement functions
Power quality functions
see Technical Descriptions of Functions, CD-ROM
(1MRS 750889-MCD)
Self-supervision RAMs
ROMs
EEPROMs
all analogue reference voltages
automatic test sequences for I/Os and HMI modules
output contact condition monitoring (all contacts)
Mechanical dimensions Width: 223.7 mm (1/2 of a 19” rack)
Height, frame: 265.9 mm (6U)
Height, box: 249.8 mm
Depth: 235 mm
External display module Width: 223.7 mm
Height: 265.9 mm
Depth: 74 mm
Weight of the unit ~8 kg