M13279-1 v10
Table 35. Pole discordance protection CCPDSC
Function Range or value Accuracy
Operate current (0–100)% of
IBase
±1.0% of I
r
Independent time delay
between trip condition and trip
signal
(0.000-60.000) s ±0.2% or ± 30 ms whichever is greater
GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8
Table 36. Voltage-restrained time overcurrent protection VRPVOC
Function Range or value Accuracy
Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio, overcurrent > 95% -
Operate time, start overcurrent at 0 to 2 x I
set
Min. = 15 ms -
Max. = 30 ms
Reset time, start overcurrent at 2 x I
set
to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start overcurrent at 0 to 10 x
I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start overcurrent at 10 x I
set
to 0 Min. = 20 ms
Max. = 35 ms
-
Independent time delay to operate at 0 to 2 x
I
set
(0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
Inverse time characteristics,
see tables 119 and 120
13 curve types See tables 119 and 120
Minimum operate time for inverse time
characteristics
(0.00 - 60.00) s ±0.2% or ±35 ms whichever is greater
High voltage limit, voltage dependent
operation
(30.0 - 100.0)% of UBase ±1.0% of U
r
Start undervoltage (2.0 - 100.0)% of UBase ±0.5% of U
r
Reset ratio, undervoltage < 105% -
Operate time start undervoltage at 2 x U
set
to
0
Min. = 15 ms -
Max. = 30 ms
Reset time start undervoltage at 0 to 2 x U
set
Min. = 15 ms -
Max. = 30 ms
Independent time delay to operate,
undervoltage at 2 x U
set
to 0
(0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
Internal low voltage blocking (0.0 - 5.0)% of UBase ±0.25% of U
r
Overcurrent:
Critical impulse time
Impulse margin time
10 ms typically at 0 to 2 x I
set
15 ms typically
-
Undervoltage:
Critical impulse time
Impulse margin time
10ms typically at 2 x U
set
to 0
15 ms typically
-
1MRK 506 384-BEN A
Line distance protection REL650 2.2
Product version: 2.2.1
ABB 49