EasyManua.ls Logo

ABB REL650 - Page 53

ABB REL650
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frequency protection
M13360-1 v15
Table 40. Underfrequency protection SAPTUF
Function Range or value Accuracy
Operate value, start function, at symmetrical three
phase voltage
(35.00-75.00) Hz ±2.0 mHz
Operate time, start at f
set
+ 0.02 Hz to f
set
- 0.02 Hz
fn = 50 Hz
Min. = 80 ms
-
Max. = 95 ms
fn = 60 Hz
Min. = 65 ms
Max. = 80 ms
Reset time, start at f
set
- 0.02 Hz to f
set
+ 0.02 Hz Min. = 15 ms
Max. = 30 ms
-
Operate time, definite time function at f
set
+ 0.02 Hz
to f
set
- 0.02 Hz
(0.000-60.000)s ±0.2% or ±100 ms whichever is greater
Reset time, definite time function at f
set
- 0.02 Hz to
f
set
+ 0.02 Hz
(0.000-60.000)s ±0.2% or ±120 ms whichever is greater
Voltage dependent time delay Settings:
UNom=(50-150)% of U
base
UMin=(50-150)% of U
base
Exponent=0.0-5.0
tMax=(0.010–60.000)s
tMin=(0.010–60.000)s
±1.0% or ±100 ms whichever is greater
( )
Exponent
U UMin
t tMax tMin tMin
UNom UMin
-
= × - +
-
é ù
ê ú
ë û
EQUATION1182 V1 EN-US (Equation 2)
U=U
measured
M14964-1 v12
Table 41. Overfrequency protection SAPTOF
Function Range or value Accuracy
Operate value, start function at symmetrical three-phase voltage (35.00-90.00) Hz ±2.0 mHz
Operate time, start at f
set
-0.02 Hz to f
set
+0.02 Hz
fn = 50Hz
Min. = 80 ms
Max. = 95 ms
-
fn = 60 Hz
Min. = 65 ms
Max. = 80 ms
Reset time, start at f
set
+0.02 Hz to f
set
-0.02 Hz Min. = 15 ms
Max. = 30 ms
-
Operate time, definite time function at f
set
-0.02 Hz to f
set
+0.02 Hz (0.000-60.000)s ±0.2% ±100 ms
whichever is greater
Reset time, definite time function at f
set
+0.02 Hz to f
set
-0.02 Hz (0.000-60.000)s ±0.2% ±120 ms,
whichever is greater
1MRK 506 384-BEN A
Line distance protection REL650 2.2
Product version: 2.2.1
ABB 53

Other manuals for ABB REL650

Related product manuals