Table 67. Number of TIMERSET instances
Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
TIMERSET 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms
GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v1
Table 68. Number of XOR instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
XOR 10 10 20
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v2
Table 69. Number of B16I instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
B16I 6 4 8
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v1
Table 70. Number of BTIGAPC instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
BTIGAPC 4 4 8
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v1
Table 71. Number of IB16 instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
IB16 6 4 8
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v1
Table 72. Number of ITBGAPC instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v3
Table 73. Elapsed time integrator with limit transgression and overow supervision TEIGAPC
Function Cycle time (ms) Range or value Accuracy
Elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is
greater
8 0 ~ 999999.9 s ±0.2% or ±100 ms whichever is
greater
100 0 ~ 999999.9 s ±0.2% or ±250 ms whichever is
greater
1MRK 506 384-BEN A
Line distance protection REL650 2.2