Configuration with TTH300 transmitters
14 SensyTemp TSP SM/TSP/SIL-EN
Configuration parameters with effect on the safety function
All configuration parameters that are changed via HMI, DTM EDD or HART communication for
disabled write protection have an effect on the safety function of the device. The parameters are
described in the operating instructions. The safety function is checked according to the SIL
safety manual.
For redundancy mode with drift monitoring, the following parameters must be set in DTM, EDD:
• Sensor type-Freestyle characteristics and Callendar van Dusen
When using these two configurations, it is necessary to check at least 3 reference points
to verify the configured characteristic. For complex curves, check several sampling points
according to complexity.
• Redundancy mode
• Pulse output enabled
• Pulse time 60 s, continuous pulse
• Drift value Configured acc. to customer application
• Drift duration max. 120 s.