EasyManua.ls Logo

ABB VBF Series - 1.0 Technical Details

ABB VBF Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
General
1.0 Technical details
This operating instruction is applicable for Outdoor circuit Breaker type VBF.
1.1 Type designation VBF 36 16 25
Outdoor Vacuum Circuit Breaker
Type VBF
Rated voltage –
Rated normal current -
Rated breaking capacity – 26.3kA
24 for 24kV
36 for 36kV
12 for 1250 Amp
16 for 1600 Amp
1.2 Specifications
1.3 Rating plate
Type VBF 36
Standard IEC – 62271-100
Rated voltage 36kV
Frequency 50 Hz
Insulation level 70/170kVp.
Normal current 1250 / 1600 Amps.
Short circuit breaking current 26.3 kA
Operating sequence 0-0.3S-CO-3 Min.-CO
Weight 800 kg.
PART B Installation, Operation & Maintenance