Cosϕ Rated current Breaking capacity
220 V AC 0.7 2.5 A 25 A
380 V AC 0.7 1.5 A 15 A
500 V AC 0.7 1.5 A 15 A
660 V AC 0.7 1.2 A 12 A
Time constant
24 V DC
1 ms 10 A 12 A
15 ms 10 A 12 A
50 ms 8 A 10 A
200 ms 4 A 7.7 A
60 V DC
1 ms 8 A 10 A
15 ms 6 A 8 A
50 ms 5 A 6 A
200 ms 4 A 5.4 A
110 V DC
1 ms 6 A 8 A
15 ms 4 A 5 A
50 ms 2 A 4.6 A
200 ms 1 A 2.2 A
220 V DC
1 ms 1.5 A 2 A
15 ms 1 A 1.4 A
50 ms 0.75 A 1.2 A
200 ms 0.5 A 1 A
Note
With the set of 10 auxiliary contacts supplied as standard, the following are available:
3 NO contacts + 5 NC contacts for fxed circuit-breakers
3 NO contacts + 4 NC contacts for withdrawable circuit-breakers
With the set of 15 auxiliary contacts (+5 contacts on request compared to the 10 sup -
plied as standard), the following are available:
for fixed circuit-breaker, as desired, 6 NO contacts + 7 NC contacts or 5 NO con -
tacts + 8 NC contacts or 3 NO contacts + 10 NC contacts
for withdrawable circuit-breakers, depending on the applications required, a maxi -
mum of 6 NO contacts + 6 NC contacts and a minimum of 5 NO contacts + 5 NC
contacts are available.
Locking magnet on the truck (-RL2)
Un
24 - 30 - 48 - 60 - 110 - 125 - 127 - 132 - 220
- 240 V–
Un
24 - 30 - 48 - 60 - 110 - 125 - 127 - 220 -
230 ... 240 V~ 50/60 Hz
Operating limits 85 … 110% Un
Inrush power (Ps) W; DC = 250 AC = 250 VA
Continuous power (Pc) DC = 5 W; AC = 5 VA
Inrush time 150 ms
Motor operator (-MS)
Characteristics
Un 24...30 - 48...60 - 110...130 - 220...250 V–
Un 100...130 - 220...250 V ~ 50/60 Hz
Operating limits
85 … 110% Un
40 kA
Inrush power (Ps)
DC=600 W; AC=600 VA
Rated power (Pn) DC=200 W; AC=200 VA
Inrush time 0.2 s
Charging time 6-7 s
Insulation voltage 2000 V 50 Hz (for 1 min)
Auxiliary contacts of the circuit-breaker
Rated insulation voltage
according to VDE 0110, Group C
660 V AC
800 V DC
Rated voltage 24 V... 660 V
Insulation-test test voltage 2.5 kV
Maximum rated current 10 A
Number of contacts 5
Stroke 6 mm ... 7 mm
Contact force 26 N
On resistance 3 m
Storing temperature range - 20° C ... + 120 °C
Operating temperature range - 20° C ... + 70 °C
Contact over temperature 20 K
Operating cycles 30,000
Unlimited short circuit stability by using fuses of max. 10 A time-lag
13