Max. 25 Nm
2
1
MEDIUM VOLTAGE PRODUCTS
4141
Fig. 13b
Fig. 13a
Racking-in
Racking-out
Note
By means of the transmission chain, truck handling carried out using the
manual lever makes the truck motor armature rotate which, behaving
like a generator, can cause inverse voltage at the connection terminals.
This may damage the permanent magnet of the motor, therefore all
the truck racking-in and racking-out operations carried out using the
manual lever must be done without power supply in the motor circuit.