CONTROL POINTS
BD
LJ,
Li
BS
Q)~
88
~
l
l
The operator drives the door against the closed position for a
preset value of 1 second.
Fire doors - adjust the lock control relay hold time to a minimum.
Sequencing
1
=
Opening and closing sequencing for pair of rebated doors
The master door opens first and then the slave.
The slave door closes first and then master door.
All impulses are connetcted to the master.
2
=
Sequential opening (stepwise opening)
Used in two doors following each other. The first door opens
from impulse and commands the second door to open.
The opening delay of the second door is adjusted in control
point 4. Note! The inside impulse connection is not operational.
3
=
Interlock controlled doors
Used in two door following each other. The first door opens
from impulse and the second door opens from impulse after
the first door Is fully closed.
The bolt information is needed in connectors 10 and 11.
MASTER
Master operator for double doors
o
=
No operation/slave operator
1
=
Master operator
=
l
Function of impulse
0= Normal
1
=
The first impulse opens the door,
second closes the door
The operator holds the door open until hold open time
expires or there is a closing impulse. Note! If hold open
time is set to 60 seconds, the operator remains open
until the second impulse is activated.
15