BATTERY OPERATION
12 VFull battery backup;
The operator and devices connected will operate during
a power failure. The operation time depends on number of openings and the current
draw of the devices fitted.
When battery backup ;s chosen, the battery is checked by the operator and the
following should be noted:
2.0V
BATTERYVOLTAGE
13.0 V
The operator tests
the battery
Battery operation will
not function
The battery is tested if the
voltage rises above 13
V
it
is operational.
If
the voltage does not rise
above 13
V
In 24 hour period,
the battery should be
replaced
The test made by the operator:
The battery is loaded with 0.4 A test load for a
30 second period. If the battery voltage drops under 11.5 V, the battery is
found unsuitable
=
> a red LEDflashes at the end of the operator indicating this
state.
During power failure ....
The operator and devices connected will operate normally. The red LEDstarts
to blink.
WHEN BATTERYVOLTAGE DROPS UNDER
8.0 V 10.5 V
,r'\,
The operator stops
Low-energy state:
The door is opened manually
and the operator closes door.
When power failure ends....
The red LEDstops blinking. If the operator stays in low-energy state, one
manual opening is required to re-enegise the operator to chosen program
selector mode.