TECHNICAL INFORMATION INFORMAZIONI TECNICHECOMPRESSOR DRIVE CFR HP - CFR HPE 35÷450
Sistema di climatizzazione e deumidicazione con
rinnovo dell’aria e compressore
termodinamico di supporto
Air conditioning and dehumidication system
with air renewal and compressor
thermodynamic support
COMPRESSOR DRIVE
CFR HP - CFR HPE
35-60-100-150-230-320-450

Questions and Answers

  • J
    Jessica BaldwinAug 11, 2025
    How to fix low airflow rate in Accorroni Air Compressor?
    • G
      George MorrowAug 12, 2025
      If the airflow rate is lower than expected in your Accorroni Air Compressor, it could be due to several reasons. The air filters might be dirty, requiring cleaning or replacement. Alternatively, the plant air resistance could be too high, necessitating a review of the air plant project. Check if the adjusting dampers are closed and, if so, open them to balance the plant. For HPE models, the fan speed might be too low; increase the fan control signal using the controller's keyboard.
  • G
    Glenda DavisAug 18, 2025
    What to do if Accorroni CFR HP 35 airflow rate is too high?
    • T
      Tiffany RobinsonAug 19, 2025
      If the airflow rate is higher than expected in your Accorroni Air Compressor, it may be due to a missing internal component, such as a filter. Ensure that all access panels are closed. Also, the plant air resistance might be lower than expected, requiring a check of the air plant project. For HPE models, reduce the fan control signal.
  • N
    Nicole SantiagoAug 26, 2025
    Why is Accorroni CFR HP 35 Air Compressor heat pump performance lower than expected?
    • S
      Stacy WhiteAug 26, 2025
      If the heat pump performance in your Accorroni Air Compressor is lower than expected, it could be due to insufficient airflow. Refer to failure 1 to resolve airflow issues. It may also be caused by wrong expansion valve setting or an improperly filled refrigeration circuit, for which you should contact a service specialist.
  • S
    Sean BurnsSep 3, 2025
    What to do if water condensate is not discharged from Accorroni CFR HP 35?
    • B
      brian23Sep 4, 2025
      If water condensate is not being discharged from your Accorroni Air Compressor, the syphon may be wrong or missing. Install a well-sized syphon to resolve this issue.

Accorroni CFR HP 35 Specifications

General IconGeneral
CategoryAir Compressor
ModelCFR HP 35
TypePiston
Power3 HP
Max Pressure10 bar
Air Delivery350 L/min
Voltage230 V
Phase1