Page 15
noitarepO
tuptuO
m
ralAepyT mralAeulaV teS
F
F
O s
i
tup
t
u
O
de
l
basi
d
noi
tc
nu
f
m
ral
A
0
1 Deviation upper- and lower-limit:
This alarm output operates when PV value is higher than
the setting value SV+(AL-H) or lower than the setting value
SV-(AL-L).
2 Deviation upper-limit:
This alarm output operates when PV value is higher than the
setting value SV+(AL-H).
3 Deviation lower-limit:
This alarm output operates when PV value is lower than the
setting value SV-(AL-L).
4 Reverse deviation upper- and lower-limit:
This alarm output operates when PV value is in the range of
the setting value SV+(AL-H) and the setting value SV-(AL-L).
5 Absolute value upper- and lower-limit:
This alarm output operates when PV value is higher than
the setting value AL-H or lower than the setting value AL-L.
6 Absolute value upper-limit:
This alarm output operates when PV value is higher than
the setting value AL-H.
7 Absolute value lower-limit:
This alarm output operates when PV value is lower than
the setting value AL-L.
8 Deviation upper- and lower-limit with standby sequence:
This alarm output operates when PV value reaches set point
(SV value )and the value is higher than the setting value
SV+(AL-H) or lower than the setting value SV-(AL-L).
9 Deviation upper-limit with standby sequence:
This alarm output operates when PV value reaches set point
(SV value) and the reached value is higher than the
setting value SV+(AL-H).
10 Deviation lower-limit with standby sequence:
This alarm output operates when PV value reaches the set
point (SV value) and the reached value is lower than the
setting value SV-(AL-L).
11 Hysteresis upper-limit alarm output:
This alarm output operates if PV value is higher than the
setting value SV+(AL-H). This alarm output is OFF when
PV value is lower than the setting value SV+(AL-L).
12 Hysteresis lower-limit alarm output:
This alarm output operates if PV value is lower than the
setting value SV-(AL-H). This alarm output is OFF when
PV value is higher than the setting value SV-(AL-L).
(Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L)
Alarm Output Configuration and Operation Table.
Communication Register List
Communication Parameters List
Controller offers a RS-485 port for serial communication.
1. Supporting transmission speed: 2400, 4800, 9600, 19200, 38400 bps.
2. Communication protocol: Modbus (ASCII).
3. Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2.
4. Available communication address: 1 to 255, 0 is broadcast address.
5. Function code: 03H to read the contents of register (Max. 3 words).
6. 06H to write 1 (one) word into register.
n
oit
anal
pxE t
ne
tnoC
s
se
rddA
4700H (R) Process value (PV) Measuring unit is 0.1, updated one time
in 0.5 second.
4701H Set point (SV) Unit is 0.1, oC or oF
4702H Upper-limit alarm 1
4703H Lower-limit alarm 1
4704H Upper-limit alarm 2
4705H Lower-limit alarm 2
4706H Upper-limit of temperature range The data content should not be higher than
the temperature range
4707H Lower-limit of temperature range The data content should not be lower than
the temperature range
4708H PB Proportional band 0.1 to 999.9, unit is 0.1
4709H Ti Integral time 0 to 9999
470AH Td Derivative time 0 to 9999
470BH Heating/Cooling hysteresis 0 to 9999
devreseRHF
0
74
~
HC0
7
4
4710H Input temperature sensor type Please refer to the contents of the
“Temperature Sensor Type and Temperature
Range” for detail
4711H Control method 0: PID (default), 1: ON/OFF, 2: manual tuning
4712H Heating/Cooling control cycle 1 to 99 second
4713H Proportional control 0% to 100%
offset error value
4714H Temperature regulation value -999 ~ 999, unit: 0.1
4715H Alarm 1 type Please refer to the contents of the “Alarm
Outputs” for detail
4716H Alarm 2 type Please refer to the contents of the “Alarm
Outputs” for detail
4717H Temperature unit display selection oC: 1 (default), oF: 0
4718H Heating/Cooling control Selection Heating: 0 (default), Cooling: 1
4719H Control Run/Stop setting Run: 1 (default), Stop: 0
471AH Communication write-in selection Communication write in disabled: 0 (default),
Communication write in enabled: 1
471BH Software version W1.00 indicates 0 x 100
1:NO ,)tluafed( 0 :FFOgnitt
eS TAH9274
)rorre oN
(
no
i
tarepo
l
amroN0 e
d
oC
ssecorp laitinI1 edoC
)
e
l
bats ton si
er
u
tare
pm
eT(
s
u
t
ats
la
itinI
2 e
do
C
detcennoc ton si rosnes erutarepmeT3 edoC
r
or
r
e
t
up
ni r
osn
e
s
er
u
ta
r
e
p
m
eT4 e
d
oC
)
R
(
H
B
27
4
sde
ecxe e
ula
v
e
r
u
tar
e
p
m
e
t
d
er
usaeM5 e
d
oC
the temperature range
r
or
re .tnI oN6 edo
C
rorrE MORPEE7 edoC
4733H CT monitor value Unit is 0.1A
Note: R means “read only” value