3.3 Displaying functions with light-emitting diodes
LED – red = overflow alarm, fault
LED – permanently lit yellow = the pump is in operation
LED – flashing yellow = the pump is in operation or in overrun
function
LED – permanently lit green = automatic mode
LED – flashing green = manual mode
LED – irregular green flashing = manual mode switched off after 2 minutes
3.4
Display
The level is always displayed in the top line. The operating hours are displayed in the bottom line when pump
delivery is not requested.
If the pump is in operation, the motor current is displayed. If any faults have occurred, they are spayed
alternately in the bottom line of the display.