MultiControl Mono
Ver. 1.1
36
8.0 Technical data
Operating voltage: 3 ~ 400V (L1, L2, L3, N, PE)
Frequency 50/60 Hz
Control voltage: 230 V/AC
Power consumption:
(contactor attracted) < 10 VA
Power consumption in quiescent state < 8 VA
Max. connected load P
2
< 4 kW (optional P
2
< 5.5 kW)
Range of electrical motor current
monitoring 0.3 – 12 A (optional 16 A)
(The limit values specified in the table under section 1.1 of the safety regulations must be observed)
230 V alarm contact 1 A
Floating alarm contact 3 A
Housing: polycarbonate
Degree of protection: IP 54
Pressure range (internal sensor): 0 - 1 mWs (optional: 0 - 2 mWs)
Temperature range: -20°C to +60°C
Dimensions: 180 x 290 x 105 mm (W x H x D)
Dimensions with cable screw connection and air connection
Fuse: 5 x 20 1AT (alarm output)
Voltage supply
for 4 - 20 mA probe: 20 V/AC
Cable screw connections: 2 x M25 x 1.5
1 x M16 x 1.5
Hose connection: 6/8 mm
(Other hose connections can also be supplied on request.)
Subject to technical changes!
9.0 Standards:
Relevant EC Directives: EC Low Voltage Directive
2006/95/EC
EC Electromagnetic Compatibility Directive
2004/108/EC
Applied harmonised standards
In particular: EN 61000 - 6 - 2: 2005
EN 61000 - 6 - 3:2007
EN 61010 - 1:2001 + Amendment 1:2002
+ Amendment 2:2004