55
Performance Data AWM-J-2010
Model: AWM20JR - ALC20CR
Heating Mode
ID DB°C
Outdoor WB°C
-9 -6 -5 6 12 15 18
TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)
15 2.446 2.446 3.074 3.074 3.284 3.284 5.590 5.590 6.847 6.847 7.476 7.476 8.105 8.105
17 2.381 2.381 3.011 3.011 3.221 3.221 5.541 5.541 6.661 6.661 7.268 7.268 7.874 7.874
19 2.316 2.316 2.948 2.948 3.158 3.158 5.492 5.492 6.474 6.474 7.059 7.059 7.644 7.644
21 2.252 2.252 2.884 2.884 3.095 3.095 5.443 5.443 6.287 6.287 6.850 6.850 7.413 7.413
23 2.250 2.250 2.837 2.837 3.032 3.032 5.201 5.201 6.100 6.100 6.642 6.642 7.183 7.183
25 2.249 2.249 2.789 2.789 2.969 2.969 4.959 4.959 5.913 5.913 6.433 6.433 6.952 6.952
27 2.248 2.248 2.742 2.742 2.906 2.906 4.716 4.716 5.727 5.727 6.224 6.224 6.722 6.722
FROST REGION
Remark:
AFR: Air fl ow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling Capacity (kW)
SHC: Sensible Heat Capacity (kW)
PI: Power Input
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2.
shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 0 °C to 46°C without pressure trip.