78
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Total capacity, TC
Interpolation Method:
x = 2.477kW
Sensible capacity, SC
Interpolation Method:
y = 1.768kW
40°C - 35°C
=
2.355kW - 2.558kW
40°C - 37°C 2.355kW - x
40°C - 35°C
=
1.655kW - 1.844kW
40°C - 37°C 1.655kW - y
Outdoor DB ° C
Indoor DB Indoor WB 35 37 40
° C ° C TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
23 15 2.558 1.844 xy2.355 1.655