ADCP-80-348
Issue 1, May 1995
Page 3
© 1995, ADC Telecommunications, Inc.
3. DSX BAY ZONING AND CROSS-CONNECT GUIDELINES
A.Cross-Connect Procedures
3.01Figure 1 is a lineup of multiple DSX bays.
Each bay is zoned in quadrants to provide the most
efficient cross-connect scheme, maximizing the use
of the vertical and horizontal wireways. When a
cross-connect assignment is required, the following
must be considered:
•If the originating equipment is in zone one or
two, the cross-connect jumper(s) must route to
the adjacent bay via the upper wireway.
•If the originating equipment is in zone three or
four, the cross-connect jumper(s) must route to
the adjacent bay via the lower wireway.
•Cross-connect jumper(s) must always be routed
through vertical and horizontal wireways when
crossing zones, except when cross-connecting
within the same DSX panel.
•When cross-connecting within the same bay from
zone one (upper left) to zone three (lower left),
the cross-connect jumper(s) must transition
through the vertical wireway only.
HORIZONTAL
JUMPER
WIREWAYS
VERTICAL
JUMPER
WIREWAYS
HORIZONTAL
JUMPER
WIREWAYS
5751-B
BAY 1 BAY 2 BAY 3
ZONE
ONE
ZONE
TWO
ZONE
THREE
ZONE
FOUR
Figure 1. DSX Bay Cross-Connect Scheme