ADCP-80-348
Issue 1, May 1995
Page 6
© 1995, ADC Telecommunications, Inc.
(continued)
5. DSX-1 CROSS-CONNECT ROUTING
PROCEDURE, continued
3.Carefully route the cross-connect jumper wire
towards the terminating equipment ensuring that
the zoning and routing procedures are followed
as defined in Section 3 and 4. Figure 4 provides a
pictorial view of the paths to be followed when
routing via the upper and lower wireways.
4.After the cross-connect has been properly routed,
cut and strip the terminating end being careful to
ensure the insulation and wire clippings do not
fall into the DSX bays.
5.Repeat Step 2 for this end of cross-connect
jumper.
6.Complete a final inspection of the cross-connect
to ensure it is neat and properly placed within the
wireways and the cable rings.
5752-C
BAY 1 BAY 2 BAY 3 BAY 4
Figure 4.
Do not pull jumper too tight — leave minimal slack
and store evenly at each end (six inches total)