EasyManua.ls Logo

ADC DSX-1 - Cross-Aisle Panel Cabling

ADC DSX-1
13 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ADCP-80-325 Issue 4 January 2001
Page 8
2001, ADC Telecommunications, Inc.
TL
T
R
T1
R1
OUT
IN
TL
T
R
T1
R1
OUT
IN
1 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
8385-A
REMOVABLE CABLE TRAY
(NOT MOUNTED BY ADC)
22.312 IN. 56.7 CM)
(REF)
23.00 IN. 58.4 CM)
(REF)
29.30 IN. ± .25 IN.
(74.4 CM ± .6 CM)
3.00 IN.
(7.64 CM)
(REF)
4.00 IN.
(10.16 CM)
MAX
1.60 IN.
(4.06 CM)
(REF)
19.80 IN.
(50.3 CM)
(REF)
G
W
BL
W
O
G
W
BL
W
O
G
W
BL
W
O
G
W
BL
W
O
W
W
W
W
W
G
W
BL
W
O
G
W
BL
W
O
W
W
W
W
W
G
W
BL
W
O
G
W
BL
W
O
W
W
W
W
W
G
W
BL
W
O
G
W
BL
W
O
TL
T
R
T1
R1
TL
T
R
T1
R1
OUT
IN
OUT
IN
1 5 95 100
COLOR SCHEME DETAIL
(EVERY 5TH CIRCUIT IS WHITE)
W
BL
O
G
WHITE
BLUE
ORANGE
GREEN
COLOR CHART
Figure 4. Typical Information Shown on Installation Drawing
4.3 Cross-Aisle Panel Cabling
4.3.1 Cross-Aisle Tie Cable Type
Recommended cable for cross-aisle cable ties is shielded twisted pair cable 26 AWG, similar
to AT&T 1249 cable. Separate cable should be used for each direction of the circuit. Ground
the cable shield at one end only.
4.3.2 Cross-Aisle Tie Cable Connections
Connect the tie cables to the wire-wrap terminals on the Cross-Aisle Panels. Figures 2 and 3
show Cross-Aisle Panel wiring in typical multi-lineup systems. One recommended method of
wiring is to connect the OUT terminals in one lineup to the IN terminals of the other lineup as
shown in Figure 5.

Other manuals for ADC DSX-1