33
2.1 Position of the stove / distance requirements
Distance requirements will only apply if the wood burning stove is to be placed close to flammable materials:
If the stove is positioned against a brick wall or other non-flammable material, there are no minimum distance
requirements. To facilitate cleaning and for the best use of the convection air, we recommend that you keep
a distance of approximately 5-10 cm to the wall.
If the wood burning stove is to be placed on a flammable material such as a wooden floor or carpet, it must
be placed on a non-flammable floor hearth. The floor hearth should extend for at least 30 cm in front of the
stove and 15 cm on each side measured from the opening of the combustion chamber.
2.2 Pipe connection
Please ensure that all local rules and regulations are complied with, including CE marking of the flue pipe.
Additionally, distance requirements to flammable material for the pipe must be respected.
A flue pipe with an internal diameter of 150 mm should be used for all Aduro stoves.