Response message format for function code 03 or 04:
Command Body
Station
Address
Function
Code
Byte
Count
Data Data
Example: Analog input #1 and #2 as floating point values where AI#1=100.0 and AI#2=55.32
01 04 08 42 C8 00 00 47 AE 42 5D
Function Code 05
Force a single coil to either ON or OFF. The requested ON/OFF state is specified by a constant in the
query data field. A value of FF 00 hex requests it to be ON. A value of 00 00 hex requests it to be OFF.
And a value of FF FF hex requests it to release the force.
Request message format for function code 05:
Command Body
Station
Address
Function
Code
Coil Address
High Byte
Coil Address
Low Byte
Force Data
High Byte
Force Data
Low Byte
Example: Force coil 3 (address 00003) ON in ADAM-6000 module
01 05 00 03 FF 00
Response message format for function code 05:
The normal response is an echo of the query, returned after the coil state has been forced.
Command Body
Station
Address
Function
Code
Coil Address
High Byte
Coil Address
Low Byte
Force Data
High Byte
Force Data
Low Byte
Function Code 06
Presets integer value into a single register.
Request message format for function code 06:
Command Body
Station
Address
Function
Code
Register Address
High Byte
Register Address
Low Byte
Preset Data
High Byte
Preset Data
Low Byte
Example: Preset register 40002 to 00 04 hex in ADAM-6000 module
01 06 00 02 00 04
Response message format for function code 06:
The normal response is an echo of the query, returned after the coil state has been preset.
Command Body
Station
Address
Function
Code
Register Address
High Byte
Register Address
Low Byte
Preset Data
High Byte
Preset Data
Low Byte