Analog I/O Modules Calibration
6-
6
ADAM 5000 IO modules User’s Manual
Calibration voltage (ADAM-5017H)
Module
Input Range Code
(Hex)
Input Range Span Calibration Voltage
00h ±10 V +10 V
01h 0 ~ 10 V +10 V
02h ±5 V +5 V
03h 0 ~ 5 V +5 V
04h ±2.5 V +2.5 V
05h 0 ~ 2.5 V +2.5 V
06h ±1 V +1 V
07h 0 ~ 1 V +1 V
08h ±500 mV +500 mV
09h 0 ~ 500 mV +500 mV
0ah 4 ~ 20 mA *(1)
5017H
0bh 0 ~ 20 mA *(1)
Table 6-2: Calibration voltage of ADAM-5017H
Note: You can substitute 2.5 V for 20 mA if you remove the current conversion
resistor for that channel. However, the calibration accuracy will be limited
to 0.1% due to the resistor's tolerance.