<7> Simple troubleshooting
FAILURE
FAILURE CAUSE
APPROACH
Check and ensure the power interface and the
power plug is plugged in place and in good contact.
Power cord is not plugged in place
Fuse burnt-out
Pull out the fuse box from the power supply
interface of the chiller, check the fuse, replace with
spare fuse if necessary and check whether the
power supply voltage is stable; Check and ensure
the power interface and the power plug is plugged in
Check the water level gauge display, add water
until the level shown in the green area; And check
whether water circulation pipe leaks.
Check water circulation pipe
Flow Alarm (panel red light is
on)use a water pipe directly
connect to the water outlet and
inlet but still without water flowing
Machine turned on but
unelectrified
Ultra-high
temperature alarm
Alarm for ultra-high room temperature
Serious problem of condensate water
Water drains slowly from outfall
during water changing
Switch the power frequently
Blocked dust gauze, bad thermolysis
Poor ventilation for air outlet and inlet
Voltage is extremely low or astable
Improper parameter settings on thermostat
Excessive heat load
The working ambient temperature is too
high for the chiller
Water temperature is much lower than
ambient temperature, with high humidity
Injection port is not open
Open the injection port
Increase water temperature or to preserve heat
for pipeline
To improve the ventilation to guarantee that the
machine is running under 40℃.
Reduce the heat load or use other model with
larger cooling capacity
To ensure there is sufficient time for refrigeration
(more than 5 minuets)
To reset controlling parameters
or restore factory settings
To improve the power supply
circuit or use a voltage regulator
To ensure a smooth ventilation for air outlet and inlet
To ensure a smooth ventilation for air outlet and inlet
Water level in the storage
water tank is too low
Water circulation pipes are blocked
or apipe bending deformation.
<4> Packing list
1.1 unit of industrial chiller.
2.1 copy of user manual.
3.1 pc of power cord.
4.1 pc of alarm signal output plug.
5.1 pc of spare fuse.
(held in the spare fuseholder of power socket.)
OFFICIAL DISTRIBUTOR UAB ELTECHNIKA
WWW.AEONLASERS.LT | WWW.AEONLASERS.LV | WWW.AEONLASERS.EE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aeon WJ-5000 Series and is the answer not in the manual?

Aeon WJ-5000 Series Specifications

General IconGeneral
BrandAeon
ModelWJ-5000 Series
CategoryChiller
LanguageEnglish