STANDARD
ThefanisoperatedusingaseparateON/OFFswitchorviaalightswitch(g.47A).
PULL CORD
Thefanisoperatedusinganintegratedpullcordswitch(g.47B).
WITH TIMER (over-run)
Thefanisprovidedwithatimercircuitwhichisadjustablefromaprox.1minuteto25
minutesviatrimmer(g.48A).
Operation:connectedaccordingtothediagraming.47C,afterthelightisswitchedon,
thefanactivateswithadelayofmax1.5seconds.Afterthelightisswitchedoff,thefan
continues to function for a pre-set period of time.
WITH HUMIDISTAT & TIMER
Thefanisequippedwithahumiditydetector,whosethresholdisadjustablefrom50%to
95%RelativeHumidity,andwithatimerwhichisadjustablefromaprox.1minuteto25
minutesviacorrespondingtrimmer(g.48B).
TurnthetrimmerHYcompletelyclockwiseandthehumidistatfunctionisdeactivated.
Automatichumidistatoperation:connectedaccordingtothediagraming.47C,when
the percentage of Relative Humidity exceeds the pre-set intervention threshold, the
fanstartsupautomatically.WhenthepercentageofRelativeHumiditygoesbelowthe
threshold,thefancontinuestofunctionforapre-setperiodoftime.
Operationwithswitchconnection:connectedaccordingtothediagraming.47C,after
thelightisswitchedon,thefanactivateswithadelayofaprox.1.5seconds.Afteritis
switchedoff,thefancontinuestofunctionforapre-setperiodoftime.
Operationviapullcordswitch(HTPCversion):connectedaccordingtothediagramin
g.47D.Byswitchingon,thefanactivateswithadelayofaprox.1.5seconds.After
switchingoff,thefancontinuestofunctionforapre-setperiodoftime.
Attention:whentherelativehumiditylevelishigherthanthepre-setthreshold,automatic
operationwithhumidistathaspriorityovermanualoperation,orratherthefancannotbe
stoppedviaswitch.
VERSIONS