Note:
Check on the basis of the load:
Delta T of a chiller at full power
Minimum choke of a chiller
Choke of chillers switched-on, beyond which the next is introduced.
Choke within which the chillers must remain switched on after one
has been disconnected.
Note:
Adjustment selection for Load or Temperature)
Filter on the holding of the increase or decrease condition of the num-
ber of chillers.
Minimum delay between switch-on of two chillers
Minimum delay between switch-off of two chillers
Note:
Check on the basis of the load:
Advance of the reset set point reset before switch-off of a chiller
Permanence of the reset set point after switch-off of a chiller
Value of the reset set point (to add to the set point)
Note:
Check on the basis of the temperature:
Settings for the functioning mode when cold
Temperature of the SUW probe/s (delivery) above which the introduc-
tion of a chiller is requested
Temperature of the SIW probe (return), below which the disconnec-
tion of a chiller is requested. This temperature is different depending
on the number of chillers switched-on