11
FUNZIONAMENTO
OPERATION
Min.: 3 °C senza acqua glicolata
Max.: 4 °C senza acqua glicolata
Default: 3 °C senza acqua glicolata
4 bbP Tempo di bypass allarme bassa pressione (sec.)
(C) Min.: 180 sec.
Max.: 360 sec.
Default: 180 sec.
5 aut Funzione partenza automatica dopo mancanza
(C) di corrente
Min.: 0 (riparte sempre nello stato di Stand-by)
Max.: 2 (riparte sempre nello stato precedente)
Default: 2
Con 0 riparte sempre in Stand-by, con 1 in On e con
2 riparte in base allo stato precedente il black-out.
6 hcP Ore funzionamento compressore (h x 10)
(C) Min.: 0
Max.: 9999
Default: 0
7 cod Codice di accesso set protetti
(C) Min.: 000
Max.: 999
Default: 000.
CR:
Parametro Sigla Descrizione
0 Fre Set temperatura ingresso acqua a freddo °C
Min.: -6 °C
Max.: 20 °C
Default: 11,5 °C
1 cal Set temperatura ingresso acqua a caldo °C
Min.: 30 °C
Max.: 60 °C
Default: 43,5 °C
2 gra Differenziale termostato °C
Min.: 0,5 °C
Max.: 3 °C
Default: 1 °C
3 ant Temperatura antigelo °C
(C) Min.: -9 °C con acqua glicolata
Max.: 4 °C con acqua glicolata
Default: 3 °C con acqua glicolata
Min.: 3 °C senza acqua glicolata
Max.: 4 °C senza acqua glicolata
Default: 3 °C senza acqua glicolata
4 bbP Tempo di bypass allarme bassa pressione (sec.)
(C) Min.: 180 sec.
Max.: 360 sec.
Default: 180 sec.
5 aut Funzione partenza automatica dopo mancanza
(C) di corrente
Min.: 0 (riparte sempre nello stato di Stand-by)
Max.: 2 (riparte sempre nello stato precedente)
Default: 2
Con 0 riparte sempre in Stand-by, con 1 in On e con
2 riparte in base allo stato precedente il black-out.
6 hcP Ore funzionamento compressore (h x 10)
(C) Min.: 0
Max.: 9999
Default: 0
7 cod Codice di accesso set protetti
(C) Min.: 000
Max.: 999
Default: 000.
b tFS Temperatura di fine sbrinamento °C
(C) Min.: 10 °C
Max.: 30 °C
Default: 15 °C.
c acP Attesa OFF-ON compressore
(C) Min.: 60 sec.
Max.: 600 sec
Default: 360 sec.
Min.: 3 °C with water
Max.: 4 °C with water
Default: 3 °C with water
4 bbP Bypass alarm time low pressure (sec.)
(C) Min.: 180 sec.
Max.: 360 sec.
Default: 180 sec.
5 aut Automatic start after power failure
(C) Min.: 0 (re-start in Stand-by status)
Max.: 2 (re-start in previous status)
Default: 2
With 0, the unit restarts in Stand-by status, with 1 in On
status and 2 in the status prior to the power failure.
6 hcP Compressor operating time (h x 10)
(C) Min.: 0
Max.: 9999
Default: 0
7 cod Protected password
(C) Min.: 000
Max.: 999
Default: 000.
CR:
Parameter Abbreviation Description
0 Fre Water inlet temperature Set point (cooling) (°C)
Min.: -6 °C
Max.: 20 °C
Default: 11,5 °C
1 cal Water inlet temperature Set point (heating) (°C)
Min.: 30 °C
Max.: 60 °C
Default: 43,5 °C
2 gra Differential thermostat (°C)
Min.: 0,5 °C
Max.: 3 °C
Default: 1 °C
3 ant Antifreeze temperature (°C)
(C) Min.: -9 °C with glycol/water solution
Max.: 4 °C with glycol/water solution
Default: 3 °C with glycol/water solution
Min.: 3 °C with water
Max.: 4 °C with water
Default: 3 °C with water
4 bbP Bypass alarm time low pressure (sec.)
(C) Min.: 180 sec.
Max.: 360 sec.
Default: 180 sec.
5 aut Automatic start after power failure
(C) Min.: 0 (re-start in Stand-by status)
Max.: 2 (re-start in previous status)
Default: 2
With 0, the unit restarts in Stand-by status, with 1 in On
status and 2 in the status prior to the power failure.
6 hcP Compressor operating time (h x 10)
(C) Min.: 0
Max.: 9999
Default: 0
7 cod Protected password
(C) Min.: 000
Max.: 999
Default: 000.
b tFS Defrosting end temperature °C
(C) Min.: 10 °C
Max.: 30 °C
Default: 15 °C.
c acP Compressor OFF-ON stand-by
(C) Min.: 60 sec.
Max.: 600 sec
Default: 360 sec.

Other manuals for AERMEC NRW Series