Why is my AIREDALE BluCube CUR092V16-1CO-0 Heat Pump compressor not operating?
- MMakayla LloydAug 16, 2025
Several factors can cause the compressor to fail. It could be due to: * Lack of power to the compressor: Check the isolator, fuses, MCBs, contactor, and control circuit wiring. * A tripped low-pressure switch (if fitted): Repair any leaks and recharge the system. If the system is completely empty, evacuate it before recharging. * Seized compressor: Replace the compressor, and investigate potential oil trapping and the general installation. * Defective compressor motor: Check winding resistances and replace the compressor. If the motor is burnt out, follow the burn-out procedure using a suction line burn-out drier.