Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data - C000 Continued
SC31D110-C000-0 SC31D130-C000-0 SC31D150-C000-0
Unit Data Full Function C000
(1)
Nominal Run Amps A 77.1 77.1 77.1
Maximum Start Amps A 77.1 77.1 77.1
Recommended Mains Fuse Size A 100 100 100
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50Hz
Control circuit VAC 24 24 24
Unit Data Cooling Only– C000
Nominal Run Amps A 15.4 15.4 15.4
Maximum Start Amps A 15.4 15.4 15.4
Recommended Mains Fuse Size A 25 25 25
Evaporator Fan - Motor - Per Fan
Motor Type EC EC EC
Quantity x Motor Size (2) kW 3 x 3.1 3 x 3.1 3 x 3.1
Full Load Amps A 4.8 4.8 4.8
Locked Rotor Amps A 4.8 4.8 4.8
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 9 9 9
Rating (Total) kW 31.5 31.5 31.5
Current Per Phase A 45.5 45.5 45.5
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.2 16.2 16.2
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
(1) Values given for function units with standard selections for heating, humidification, supply air fans.
C000