CAPACITY DATA
Standard Dry Cooler Fan
Water Entering / Leaving
Ambient
Temperature °C 25°C 30°C 35°C 40°C 45°C
Output
(kW)
Output
(kW)
Output
(kW)
Output
(kW)
Output
(kW)
DR55
35°C/30°C 55 - - - -
40°C/35°C 91.2 54.8 - - -
45°C/40°C 126.3 90.4 54.4 - -
50°C/45°C 161.2 125.1 89.6 54 -
55°C/50°C 196 159.5 123.8 88.7 53.7
DR70
35°C/30°C 74.7 - - - -
40°C/35°C 122.6 74.2 - - -
45°C/40°C 169.4 121.5 73.7 - -
50°C/45°C 215.8 167.6 120.3 73.1 -
55°C/50°C 262.1 213.4 165.8 119.2 72.6
DR75
35°C/30°C 72.6 - - - -
40°C/35°C 121.5 72.3 - - -
45°C/40°C 169.2 120.6 72 - -
50°C/45°C 216.6 167.7 119.6 71.6 -
55°C/50°C 263.8 214.5 166.2 118.7 71.2
DR95
35°C/30°C 98.5 - - - -
40°C/35°C 163.3 97.9 - - -
45°C/40°C 226.7 162 97.4 - -
50°C/45°C 289.7 224.6 160.6 96.7 -
55°C/50°C 352.6 286.9 222.5 159.3 96.1
(1) Output kW refers to the dry cooler heat
rejection
Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C -20°C
Maximum Ambient Air DB °C +48
Optional On/Off Head Pressure Control
Minimum Ambient Air DB °C -0°C
Maximum Ambient Air DB °C +48
(1) For conditions outside those quoted, please contact Airedale.
(2) Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.
OUTDOOR