EasyManua.ls Logo

AIREDALE SmartCool D - Water Cooled Models (W2 W2) Performance Data; W2 W2 Cooling Duties Performance Data

Default Icon
218 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SmartCool
TM
- D
Precision Air Conditioning
94
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Water Cooled Models (W2W2)
Performance Data Water Cooled Models
Cooling Duties
Cooling Capacity (1)
Condenser Entering / Leaving Temperature - Based on T of 5°C
Air On °C DB
25°C/30°C 30°C/35°C 35°C / 40°C 40°C/45°C
/%RH
TC
(kW)
SC
(kW)
THR
(kW)
TC
(kW)
SC
(kW)
THR
(kW)
TC
(kW)
SC
(kW)
THR
(kW)
TC
(kW)
SC
(kW)
THR
(kW)
SC19D055-W2W2-0
2 x DR40
22/50 52.4 48.8 67.2 52.4 48.8 67.2 51.9 48.6 67.1 49.2 47.4 66.4
24/45 53.5 52.4 68.3 53.5 52.4 68.3 53.0 52.2 68.2 50.2 50.2 67.4
26/40 54.5 54.5 69.3 54.5 54.5 69.3 54.0 54.0 69.2 51.2 51.2 68.4
SC19D070-W2W2-0
2 x DR55
22/50 65.2 59.8 83.9 65.2 59.8 83.9 65.2 59.8 83.9 63.1 58.8 83.3
24/45 66.9 64.2 85.6 66.9 64.2 85.6 66.9 64.2 85.6 64.7 63.4 84.9
26/40 68.3 68.3 87.0 68.3 68.3 87.0 68.3 68.3 87.0 66.1 66.1 86.3
SC19D080-W2W2-0
2 x DR55
22/50 74.2 67.2 95.8 74.2 67.2 95.8 74.2 67.2 95.8 71.5 66.0 94.9
24/45 76.1 72.2 97.7 76.1 72.2 97.7 76.1 72.2 97.7 73.3 71.0 96.7
26/40 77.7 77.5 99.3 77.7 77.5 99.3 77.7 77.5 99.3 74.8 74.8 98.3
SC25D080-W2W2-0
2 x DR55
22/50 75.7 69.8 97.3 75.7 69.8 97.3 75.7 69.8 97.3 72.9 68.4 96.3
24/45 77.6 75.1 99.2 77.6 75.1 99.2 77.6 75.1 99.2 74.7 73.6 98.1
26/40 79.3 79.3 100.8 79.3 79.3 100.8 79.3 79.3 100.8 76.3 76.3 99.7
SC25D090-W2W2-0
2 x DR70
22/50 82.4 76.5 106.9 82.4 76.5 106.9 82.4 76.5 106.9 79.7 75.2 106.0
24/45 84.6 82.3 109.1 84.6 82.3 109.1 84.6 82.3 109.1 81.7 80.9 108.1
26/40 86.4 86.4 110.9 86.4 86.4 110.9 86.4 86.4 110.9 83.5 83.5 109.9
SC25D100-W2W2-0
2 x DR70
22/50 93.9 85.6 122.1 93.9 85.6 122.1 93.9 85.6 122.1 90.6 83.8 121.3
24/45 96.3 91.7 124.5 96.3 91.7 124.5 96.3 91.7 124.5 92.9 90.0 123.6
26/40 98.3 98.3 126.6 98.3 98.3 126.6 98.3 98.3 126.6 94.8 94.8 125.6
SC31D100-W2W2-0
2 x DR70
22/50 95.8 86.2 124.1 95.8 86.2 124.1 95.8 86.2 124.1 92.1 84.4 122.8
24/45 98.3 92.5 126.6 98.3 92.5 126.6 98.3 92.5 126.6 94.5 90.7 125.3
26/40 100.3 99.3 128.7 100.3 99.3 128.7 100.3 99.3 128.7 96.5 96.5 127.3
SC31D120-W2W2-0
2 x DR95
22/50 109.6 99.1 141.7 109.6 99.1 141.7 109.6 99.1 141.7 105.0 96.9 140.2
24/45 112.4 106.4 144.6 112.4 106.4 144.6 112.4 106.4 144.6 107.7 104.3 143.0
26/40 114.8 114.4 147.0 114.8 114.4 147.0 114.8 114.4 147.0 109.9 109.9 145.3
SC31D130-W2W2-0
2 x DR95
22/50 117.2 105.7 151.6 117.2 105.7 151.6 117.2 105.7 151.6 112.2 103.4 150.2
24/45 120.2 113.4 154.7 120.2 113.4 154.7 120.2 113.4 154.7 115.0 111.1 153.1
26/40 122.8 122.1 157.4 122.8 122.1 157.4 122.8 122.1 157.4 117.5 117.5 155.7
TC=Total Cooling SC=Sensible Cooling THR=Total Heat of Rejection
(1) All data quoted is gross
(2) Deduct fan gain for net duties, refer to Mechanical Data
(3) Interpolate for water temperatures between those quoted, do not extrapolate
(4) Water flow rate (l/s)= THR/(4.19 x T) at 100% Water
W2W2