1569H051 Ed.03
Description
Units
Min
Def
Max.
d0
Defrost frequency (Time between two starts)
(h.)
0
6
96
d1
Maximum defrost duration (0=defrost deactivated)
(min.)
0
15
255
d2
Type of message during defrost:
0=Current temperature; 1=Temperature at start of defrost; 2=Display dEF message
0
2
2
d3
Maximum duration of message
(Time added at the end of the defrost process)
(min.)
0
5
255
d4
Defrost end temperature (probe 2) (If P4 ¹ 1)
(ºC/ºF)
-45
8.0
99,0
d5
Defrost on equipment start-up :
0=NO, First defrost as per d0
1=YES, First defrost as per d6
0
0
1
d6
Defrost start delay on equipment start-up
(min.)
0
0
255
d8
Calculated time between defrost period :
0=Total actual time; 1 =Sum of times the compressor is on
0
0
1
d9
Drip time at end of defrost
(compressor and fans off) (if P4 ¹ 1)
(min.)
0
1
255
EP
Exit Level 1
Level 1.- DEFROST CONTROL
Level 2
Description
Units
Min
Def
Max.
F0
Fan shut-down temperature as per probe 2
(if P4 ¹ 1)
(ºC/ºF)
-45
45
99,0
F1
Probe 2 differential (If P4 ¹ 1)
(ºC/ºF)
0,1
2,0
20,0
F2
Stop fans when stopping compressor 0=No, 1=Yes
0
1
1
F3
Fan status during defrost:
0=Off; 1=On
0
0
1
F4
Starting delay after defrost (if F3=0)
Will only operate if it is higher than d9
(min.)
0
3
99
EP
Exit Level 1
Level 2
Level 1.- FAN CONTROL