1569H051 Ed.03
9.- Parameters
The parameters are grouped into 6 sections depending on their function. Press the N + Q keys for 10 seconds to
access it.
The Def. column shows factory-set default parameters.
Temperature values are expressed in ºC. (Equivalent temperature in ºF)
Level 1.- REGULATION AND CONTROL
Temperature Adjustment (Set Point)
Calibrating probe 1 (Offset)
Probe 1 differential (Histeresis) (Histéresis)
Upper blocking of the set point
(cannot be set above this value)
Lower blocking of the set point
(cannot be set below this value)
Type of delay for protection of the compressor
0=OFF/ON (since the last disconnection);
1=OFF-ON/ON-OFF (since the last shut-down /start-up)
Protection delay time
(value of the option selected in parameter C4)
Status of COMP. relay with probe fault :
0=OFF; 1=ON; 2=Average based on last 24 hours prior to probe fault;
3=ON-OFF as prog. C7 and C8
Time relay ON in case of faulty probe:
(If C7=0 and C8¹0, the relay will always be OFF deenergised)
Time relay OFF in case of fault of probe 1:
(If C8=0 y C7¹0, the relay will always be ON energised)
Maximum duration of the continuous cycle mode.
(0=disabled)
Variation of the set point (SP) in continuous cycle mode, when it reaches this point
(SP+C10), it reverts to the normal mode. (SP+C10 ³ C3)
(0=OFF) The value of this parameter is always negative, except if it is 0
Idle time of the digital input for the change Set Point function to be activated
(Only if P10 or P11 =1) (0=OFF)
Variation of the set point (SP) when the change set point function is active.
(SP+C12 £ C2) (0= disabled)