Magnetic Input Frequency | 10, 000 Hz (max) |
---|---|
Display Type | LCD |
Communication Ports | RS232, RS485 |
Storage Temperature Range | -40 °C to +85 °C |
Dimensions | 240 mm x 181 mm x 42 mm |
Number of Inputs | 6 |
Battery Voltage Monitoring | Yes |
Programmable Alarms | Yes |
Input Voltage | 8 to 35 V DC |
DC Supply | 8 to 35 V continuous |
Cranking Dropouts | Able to survive 0 V for 50 ms providing supply was at least 10 V before dropout and supply recovers to 5 V |
Magnetic Input Range | 0.5 V to 70 V RMS |
Output Voltage | 24V DC |
Protection Class | IP65 (front) |
Engine Start Modes | Manual, Automatic |
Functions of the Stop/Reset button and Manual mode for generator control.
Operation modes (Auto, Test) and Start button function for generator management.
Features for silencing alarms, testing LEDs, and navigating the module interface.
Module automatically starts, stops, and manages the generator based on requests.
Manual control of the generator set, including starting, stopping, and load switching.
Procedure for performing an on-load test of the generator set.
Non-critical alarm conditions that alert the operator to undesirable situations.
Pre-warning alarms that indicate a potential for more serious alarm conditions.
Alerts when generator output current exceeds a pre-set warning level.
Latching alarms that stop the generator and require manual reset after fault rectification.
Initiates shutdown when generator output current exceeds a critical trip level.
Controlled stops that de-energize generator output and initiate cooling before shutdown.