Document Nr.: A6.5.048 / 02Replacement for A6.5.048/01 and A6.5.049/01 Date: 02.02.2004 DWG Nr.: /PCN 0715180
ALCO CONTROLS
Emerson Electric GmbH & Co. OHG
Heerstr.111 - D 71332 Waiblingen
Tel.: 07151 509-0 - Fax.: -200
Operating Instructions
Pressure Controls Series PS1 / PS2
GB
For application in refrigeration systems and heat
pumps.
!
Safety instructions:
Read installation instructions thoroughly.
Failure to comply can result in device failure,
system damage or personal injury.
It is intended for use by persons having the
appropriate knowledge and skill.
Before opening any system make sure pressure
in system is brought to and remains at
atmospheric pressure.
Ensure supply voltage and current of electric
device match rating on PS1/PS2 name plate.
Disconnect supply voltage from system and
PS1/PS2 before installation or service.
Do not exceed test pressure.
Keep temperatures within nominal limits.
Function/Type of switch (Fig. 1):
Fig. 1a: automatic reset function
Fig. 1b: manual reset function for low pressure reset
Fig. 1c: manual reset function for high pressure reset
PS1/PS2 Pressure switches are equipped with
SPDT snap action contacts switching from 1-2 to 1-
4 on rising and from 1-4 to 1-2 on falling pressure.
Reaching the preset switch point on rising pressure,
contact 1-2 breakes while contact 1-4 makes and
vice versa on falling pressure.
PS1/PS2 with manual reset (high pressure/low
pressure reset): Reaching the preset switching point
contact 1-4 breakes (low pressure switch) or
contact 1-2 makes (high pressure switch) and locks
in this position. After the pressure rises or drops by
a fixed differential the switch can be reset by
pushing the reset button.
PS1/PS2 with manual reset are “trip-free”.
Mounting (Fig. 2):
PS1/PS2 controls may be installed by using a
mounting plate or as a wall-mounted device against
a flat surface.
Use universal thread M4 or UNC8-32 mounting
holes for installation via mounting plate.
Use the standard mounting holes at the backside for
wall mounting.
Use mounting screws supplied with control.
Mounting screws must not penetrate control
backside by more than 8 mm to ensure proper
operation.
Do not use PS1/PS2 in pulsating operating
conditions!
In order to achieve protection class IP44, the
following instructions must be observed:
Cover must be closed and cover screw fastened
Control must be mounted against a flat surface so
that all openings on the housing backside are fully
covered
Mounting direction:
Any direction except upside down
Pressure connection (Fig. 3):
Connection of the pressure side depends on the
exact model / pressure connector.
Connectors A, C, F and S: Do not apply torsional
load to pressure connnector; use second spanner to
counter-balance torque when tightening pressure
connection.
Connector A: high pressure versions (pressure
range ‘5’) are equipped with a snubber to dampen
pulsations.
When connecting PS1/PS2 to the hot gas line of a
refrigeration system, a pipe, capillary or flexible
tube of at least 80 mm shall be used to allow
sufficient temperature drop between refrigeration
line and pressure switch bellows.
K-type connectors: use copper gasket supplied with
control.
Leakage test:
After completion of installation, a test pressure must
be carried out as follows:
- According to EN378 for systems which must
comply with European pressure equipment directive
97/23/EC
- To maximum working pressure of system for other
applications
Warning:
- Failure to do so could result in loss of refrigerant
and personal injury.
- The pressure test must be conducted by skilled
persons with due respect regarding the danger
related to pressure.
Maintenance/Service:
In case of repair work or replacing the control always
use new gasket
Electrical connection (Fig. 4):
Range spindle Electrical terminals
Lockplate Check-out lever
Differential spindle Cable entry grommet
Note: Comply with local electrical regulations when
conducting electrical wiring. Wire size must match
the electrical load connected to the switch contacts.
Feed cables through rubber grommet at switch
bottom.
Optionally, the rubber grommet may be replaced by
a standard PG 13.5 cable gland.
Connect wires to terminals 1, 2 and 4 by taking into
account switch functions as shown in Fig. 1a to 1c.
Fasten terminal screws with torque 1.2 Nm max.
For electronic applications with low electrical loads
(voltage <24 V and
current <50 mA) gold plated
contacts are recommended.
Setpoint adjustment (Fig. 5):
Upper setpoint Upper setpoint
Lower setpoint Lower setpoint
Differential = constant Differential = variable
Turning range spindle
Turning differential spindle
PS1/PS2 pressure switches come with individually
adjustable range and differential depending on the
exact model.
Manual reset switches always have a fixed
differential.
Use a flat screw driver or a ¼” refrigeration
(square) wrench to adjust setpoints as described
below.
Adjust upper setpoint using the range spindle.
Adjust lower setpoint by turning the differential
spindle.
Upper setpoint – Differential =
Lower setpoint
A separate gauge must be used for exact adjustment
of the setpoints. The integrated display scale can
only be used for obtaining approximate settings.
When changing the upper setpoint the lower
setpoint must be re-checked.
Refer to the ALCO catalogue for standard factory
settings.
Manual reset / Universal reset (Fig.6):
Manual reset (external): press the reset button
as
indicated by Fig. 6a.
Manual reset (internal): remove the housing cover and
press the reset button
as indicated by Fig. 6b.
Note that the reset is ‘trip-free’, i.e. reset is only
possible if the pressure has reached its reset
treshold.
Universal reset: remove the cover and change the
universal toggle to the desired position (manual
or auto reset ).
Check-out lever
(Fig. 4)
Use the check-out lever to manually override the
electrical contact position for testing out the
system.
Use the check-out lever on low pressure switches to
manually override the electrical contact position for
evacuating the refrigeration system.
Standards
EN 12263 (DIN 32733): specific models
Pressure Equipment Directive PED 97/23/EC,
Category IV for all devices with TÜV approval
under EN12263 (DIN 32733)
Low Voltage Directive LVD 73/23/EWG;
93/68/EWG; EN 60947-1; EN 60947-5-1
UL/CSA: all models
0035 marking for devices under PED
marking for devices under LVD
Technical data:
Protection class: IP44 (IEC 529/EN 60529)
Ambient temperature (housing): -50°C to +70°C
Storage / transportation temperature:-50°C to
+70°C
Medium / allowable temperature TS: -50°C to
+70°C
Operating pressure: -0.9 to 31 bar
Test pressure PT: see type code / pressure range
Max. allowable pressure PS:see type code / pressure
range
Vibration resistance: 4g (10...1000 Hz)
Electrical rating
Heating load (AC1): 24 A / 230 V AC
Inductive load (AC15): 10 A / 230 V AC
Inductive load (DC13): 0.1 A / 230 V DC
3 A / 24 V DC
Start-up (AC3): 144 A / 230 V AC
Motor rating (FLA): 24 A / 230 V AC
Locked rotor (LRA): 144 A / 230 V AC
Medium compatibility: HFC, HCFC
not released for inflammable refrigerants
Type code:
PS1 - ! "
#, PS2 - ! " # e.g. PS1-A 5 A
! Function
A = Pressure control, automatic
B = Pressure cut out, external manual reset,
V/EN12263 approval,
C = (PS2) Left: pressure limiter, automatic,
V/EN12263. Right: pressure cut out,
external manual reset, TÜV/EN12263
G = (PS2) Left: pressure cut out, external man reset,
V/EN12263. Right: safety pressure cut out,
internal manual reset, TÜV/EN12263
L = (PS2) Left: automatic pressure control.
Right: pressure control, extern. manual reset
M =(PS2) Left: automatic pressure control.
Right: convertible reset from R to A
R = Pressure control, external manual reset
S = Safety pressure cut out, internal manual reset,
V/DIN32733 approval
T = (PS2) Left: pressure limiter, automatic, TÜV/
DIN32733. Right: safety pressure cut out,
internal manual reset, TÜV/DIN32733.
U = Convertible from function ‘R’ to ‘A’
W = Pressure limiter, automatic,
V/DIN32733 approval
NOTE: Function types B, R or S in combination with
pressure range 1, 2 or 3 have a low pressure manual
reset function and latch with falling pressure. Function
types B, R, S in combination with Pressure Range 4 or 5
have a high pressure manual reset function and latch
with rising pressure
" Pressure range (Fig. 7)
(PS: max. allowable pressure / PT: test pressure)
# Pressure connection (Fig. 3)
A =
7
/
16
"-20 UNF, male
C = R
1
/
4
" male, stainless steel with steel bellows
K = cap. tube, nut
7
/
16
"-20 UNF, schrader valve opener
R = R
1
/
4
" male, brass