4. After powerup, check the status of the controller:
5. When the update is successful:
– restore all connections to the controller
– download the program back into memor
y and make certain that it
runs properly
Your firmware update is complete. If you have any questions, call Rockwell
A
u
tomation Technical Support at 440.646.3223.
PLC-5, ControlNet, Allen-Bradley, DH+, PLC-5/20, -5/20C, -5/30, -5/40, -5/40C, -5/60, -5/80, -5/80C, -5/20E,
-5/40E, -5/80E, and RSLinx are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
If: Then:
PROC LED is solid red and CH1A DH+ LED is blinking green Update is complete. Proceed to Step 5 below.
PROC LED is flashing red. CH1A is not flashing green Call Rockwell Automation Technical Support at 440.646.3223. Send
cont
roller in for repair.
PROC LED is flashing red and green Repeat the ControlFLASH procedure
You get a PLC Mismatch error: Incorrect Selection of PLC Device The controller you selected and the controller you are trying to update
are differ
ent. Repeat the procedure and select the correct controller.
You get an Error Reading Serial Number: Invalid Serial Number The PLC-5 programmable controller was previously updated
in
correctly. Send it in for repair.